Features Of OBTS 80KV MOTORISED
- 2 % Accuracy.
- Compact and rugged & Quick and Easy to operate.
- Good Locking, Sturdy Cabinet & Up-to 120 KV Output Voltage.
- Excellent Weight / Performance Ratio & Moving Coil A.C Rectifier type Volt Meter.
- This Test Set to measure Breakdown Voltage of any kind of Transformer oil.
TECHNICAL SPECIFICATION
SPECIAL FEATURES
INDICATIONS
PROTECTION SCHEME
ACCESSORIES
TECHNICAL SPECIFICATION
Model | SBE – OBTS-80 | SBE – OBTS-100 | SBE – OBTS-120 |
CAPACITY | 80 KV | 100 KV | 120 KV |
VOLTAGE RANGE | 0 – 80 KV | 0 – 100 KV | 0 – 120 KV |
INPUT SUPPLY VOLTAGE | 230 VOLT, ± 10%, Single Phase, 50 Hz, AC. | ||
CAPACITY | 800 VA | 1000 VA | 1200 VA |
OPERATING TEMPERATURE | 0 ° C – 55 ° C | ||
DISPLAY | Analog / Digital as per Customer Requirement. | ||
METER ACCURACY | ± 2% of reading. | ||
RATE OF RISE | 2 KV/Seconds. | ||
COOLING | Resin Cast, Air Natural Cooled. | ||
BREAKDOWN | 1 Minute Withstand or Momentary Automatic Breakdown. | ||
OPERATION | Motorized cum Manual. | ||
PROTECTION | Overload Protection, Zero Start Interlock, Door Interlock. | ||
TEST SET STANDARD | IS 6792 | ||
DIMENSION (APPROX.) | 500 mm (L) X 475 mm (B) X 525 mm (W) |
SPECIAL FEATURES
- Variable Test Voltage Setting Knob.
- Capable to test up to 80/100/120 KV.
- Available in Motorized cum Manual Mode.
- Moving coil AC Rectifier type voltmeter.
- ‘MEMORY’ Push Button to observe the Breakdown Voltage.
INDICATIONS
- ‘MAINS ON’ Indication.
- ‘HT ON’ Indication.
- ‘VARIAC NOT AT ZERO’ Indication.
PROTECTION SCHEME
- Overload Protection.
- Short Circuit Protection.
- Door Interlock Protection.
- ‘Zero Start Interlock’ Protection.
ACCESSORIES
- User Manual.
- EARTH Interlock.
- Mains Supply Cord.
- Oil Pot with Electrodes.
- GO – NO – GAUGE.